In conjunction with our partners at Euro 2000, this article explains what a flexible conduit system is, as well as the characteristics and various types available for your project. read our complete guide to flexible conduits here...
Let’s start with a conduit system, and let’s review it with the help of an explanatory figure.
What is it? It is a closed wiring system consisting of fittings for protecting and managing cables in electrical or communication systems, allowing them to be inserted and/or replaced but not to be inserted laterally.
There are several tests to assess the quality of a flexible conduit and its features. In particular, it is necessary to determine:
At Euro 2000, our quality control department carries routine in-house testing for flexible conduit according to EN IEC 61386.
The test samples are positioned on a flat steel support, and an intermediate steel piece, as shown in Figure 3, is placed at the center of the sample. A continuously increasing compressive force is applied to the intermediate piece, reaching the values shown in Table 1 within 30 seconds. After the force (according to the classification) has been applied for (60 ± 2) seconds, the outer diameter of the sample is measured where flattening occurred without removing the force. The difference between the initial outer diameter and the diameter of the flattened sample must not exceed 25% of the initial outer diameter measured before the test.
The force and the intermediate piece are then removed, and 60 seconds after removal, the outer diameter of the sample is measured again where flattened. The difference between the initial diameter and the diameter of the flattened sample must not exceed 10% of the outer diameter as measured before the test. After the test, the specimens must not show visible cracks without further magnification.
A pipe sample and two end fittings are assembled according to the manufacturer’s instructions so that the total length (L) is about 300 mm.
The assembly is subjected to continuous and increasing tensile force for 30 to 40 seconds up to the value specified in Table 1. After 2 min ± 10 s the force is removed. If elongation occurs, the manufacturer shall provide instructions to assist in a safe installation. For conduit systems where the tensile strength is not stated, the tensile strength of the joint must meet the requirements of the applicable tests. After testing, the end fittings must remain properly assembled to the pipe, and there must be no visible damage.
If you would like to discuss your flexible conduit requirements with our team, don't hesitate to get in touch with us today.